Modbus Function Code 07 (0x07): Read Exception Status Specification & Hex Guide

When polling dozens of legacy RTUs over slow 9600-baud RS-485 serial lines, SCADA masters need the fastest possible way to check whether a remote PLC or controller has an active alarm, low backup battery, or fault latch. Instead of issuing a multi-byte Function Code 01 (Read Coils) poll with starting addresses and counts, the Modbus Application Protocol Specification V1.1b3 provides Function Code 07 (0x07) — Read Exception Status.

FC 07 packs eight device-specific status bits into a single byte response using a 1-byte request PDU—making it one of the smallest packets in industrial automation. This guide covers the protocol rules, hex byte layouts, bit-decoding table, Python pymodbus code, and how to test frames in ModbusSimulator.

1. How Function Code 07 Works (Serial Line Specification)

Per the Modbus specification, Function Code 07 is a Serial Line only function (Modbus RTU and Modbus ASCII) designed for quick polling of 8 predefined Exception Status outputs inside a slave controller.

  • No Address or Quantity Fields: The request PDU contains only the function code 0x07. Which internal coils or fault bits map to bits 0–7 is vendor-defined (historically Modicon 984/584 mapped 8 specific system coils).
  • 1-Byte Bitmask Response: The slave replies with 0x07 plus a single Output Data byte (bits 0 through 7, LSB = bit 0, MSB = bit 7).
  • Not a Protocol Exception Response: Unlike an error frame (where the MSB of the function code is set to 1, e.g., 0x83 + Modbus exception code), FC 07 reads application-level health flags.

2. Request & Response Hex Frame Analysis

Below is a complete Modbus RTU transaction querying Slave ID 1 (0x01), which returns Exception Status byte 0x6D (binary 0110 1101):

Modbus RTU Request Frame (4 Bytes Total)

[Slave ID] [Function Code] [CRC-16 Lo Hi]
    01           07            41 E2

Modbus RTU Normal Response Frame (5 Bytes Total)

[Slave ID] [Function Code] [Output Data] [CRC-16 Lo Hi]
    01           07             6D           E3 9F
Bit Position Binary Value (0x6D) Example Vendor Meaning
Bit 0 (LSB)1Controller Run / Online
Bit 10Memory Battery OK
Bit 21I/O Bus Warning Active
Bit 31High Temperature Alarm
Bit 40No Watchdog Timeout
Bit 51Power Brownout Latched
Bit 61Remote Mode Selected
Bit 7 (MSB)0No Fatal Fault

3. Standard Exception Codes for FC 07

If the slave cannot process Function Code 07, it responds with function code 0x87 (0x07 | 0x80) and a 1-byte exception code:

Exception Code Name Cause in FC 07
0x01 Illegal Function Most common on modern TCP-only PLCs that omit legacy serial-only FC 07 support.
0x04 Server Device Failure Internal hardware diagnostic bus or status register bank failed to respond.

4. Python Implementation Using Pymodbus (RTU Serial)

from pymodbus.client import ModbusSerialClient

def poll_exception_status(port="COM3", baudrate=9600, slave_id=1):
    client = ModbusSerialClient(port=port, baudrate=baudrate, bytesize=8, parity="N", stopbits=1, timeout=1.0)
    if not client.connect():
        raise RuntimeError(f"Unable to open serial port {port}")

    resp = client.read_exception_status(slave=slave_id)
    if resp.isError():
        print(f"FC 07 error: {resp}")
    else:
        status_byte = resp.status
        print(f"Exception Status Byte: 0x{status_byte:02X} (bin: {status_byte:08b})")
        for bit in range(8):
            print(f"  Bit {bit}: {(status_byte >> bit) & 1}")

    client.close()

if __name__ == "__main__":
    poll_exception_status()

5. Testing Serial & TCP Frames With ModbusSimulator

Before commissioning RS-485 field buses or migrating legacy Modicon PLCs, inspect raw serial frames and timing using ModbusSimulator (Windows Modbus emulator, Modbus slave simulator, and Modbus TCP simulator):

  • Verify baud rate, parity (8-N-1 vs 8-E-1), and CRC-16 checksums without physical hardware.
  • Watch real-time hex traffic logs to distinguish normal FC 07 status bytes from 0x87 exception responses.
  • Compare FC 07 polling against FC 08 (Diagnostics) and FC 17 (Report Server ID).

Debug Modbus RTU & TCP Packets on Windows

Download ModbusSimulator for Windows — unified Master + Slave simulator with raw hex packet capture and virtual COM testing.

Download Free 30-Day Trial

Frequently Asked Questions

What is Modbus Function Code 07 (0x07)?

Function Code 07 is Read Exception Status, a serial-line command that reads eight predefined status bits (1 byte) from a remote slave device in a single compact frame.

Why does a modern Modbus TCP PLC return Exception 01 for FC 07?

Per the Modbus spec, FC 07 is defined for Serial Line (RTU/ASCII). Many Ethernet-native Modbus TCP devices do not implement it and return 0x01 Illegal Function.

Is FC 07 the same as a Modbus Exception Code?

No. A Modbus Exception Response uses function code 0x80 + original_FC to report an error. FC 07 is an active query reading 8 vendor-defined status flags.

How many bytes is an FC 07 RTU request?

Just 4 bytes on the wire: 1-byte Slave ID, 1-byte Function Code (0x07), and 2-byte CRC-16 checksum.