Modbus Function Code 20 (0x14): Read File Record Specification & Hex Guide

Standard Holding Registers (FC 03) address a flat 65,536-word register space, which quickly runs tight in protection relays, flow computers, and batch recorders storing multi-megabyte oscillography or historical archives. To retrieve structured multi-file records cleanly, the Modbus Application Protocol Specification V1.1b3 defines Function Code 20 (0x14) — Read File Record.

Function Code 20 organizes extended 6xxxx memory into numbered files (1 to 65,535) containing up to 10,000 sequential 16-bit registers per file—and lets a master bundle multiple non-contiguous file reads inside a single request PDU. This guide breaks down the sub-request format, hex PDU framing, exception rules, Python pymodbus code, and simulation in ModbusSimulator.

1. How Function Code 20 Works (V1.1b3 Specification)

Unlike single-range register reads, Function Code 0x14 carries a 1-byte Byte Count (0x07–0xF5, i.e., 7 to 245 bytes) followed by one or more 7-byte Sub-Request blocks:

  • Reference Type (1 Byte): Must be 0x06 for extended file record space.
  • File Number (2 Bytes): Unsigned 16-bit integer from 0x0001 to 0xFFFF identifying which archive file to query.
  • Record Number (2 Bytes): Starting 0-based record index inside that file (0x0000 to 0x270F / 0–9999).
  • Record Length (2 Bytes): Number of consecutive 16-bit registers to read starting at Record Number.

2. Request & Response Hex Frame Analysis

Suppose a SCADA master requests 2 registers from File Number 4 (0x0004) starting at Record Number 1 (0x0001) on Unit ID 1, and the slave returns register values 0x0DFE and 0x0020.

Modbus RTU Request Frame (11 Bytes)

[Slave] [FC] [ByteCnt] [Ref] [FileNo] [RecNo] [RecLen] [CRC-16]
  01     14     07      06    00 04    00 01   00 02    [CRC]

Modbus TCP Request ADU (15 Bytes)

[Trans ID] [Proto] [Len]  [Unit] [FC] [ByteCnt] [Ref] [FileNo] [RecNo] [RecLen]
  00 01     00 00  00 09   01     14     07      06    00 04    00 01   00 02

Modbus TCP Normal Response ADU

[Trans ID] [Proto] [Len]  [Unit] [FC] [RespLen] [SubLen] [Ref] [Word 0] [Word 1]
  00 01     00 00  00 09   01     14     07        05     06    0D FE    00 20
Response Field Hex Value Size & Meaning
Function Code0x141 byte — Read File Record (decimal 20)
Resp. Data Length0x071 byte — Total bytes following in PDU (1 + 1 + 4 + 1 = 7)
File Resp. Length0x051 byte — Sub-response length including Reference Type (1 + 2 × 2 = 5)
Reference Type0x061 byte — Confirms extended file record memory
Record Data0D FE 00 204 bytes — Two 16-bit Big-Endian register values (3582 and 32)

3. Standard Exception Codes for FC 20

If any sub-request fails validation, the device responds with function code 0x94 (0x14 | 0x80) and a standard Modbus exception code:

Exception Code Name Root Cause in FC 20
0x01Illegal FunctionPLC or meter does not support Function Code 20.
0x02Illegal Data AddressFile Number does not exist or Record Number + Length exceeds file bounds.
0x03Illegal Data ValueByte Count not a multiple of 7 (+0), Reference Type != 0x06, or PDU overflow.
0x04Server Device FailureFlash/EEPROM archive read error inside the remote device.

4. Python Implementation Using Pymodbus

from pymodbus.client import ModbusTcpClient
from pymodbus.file_message import FileRecord

def read_plc_file_record(host="127.0.0.1", port=502, file_no=4, record_no=1, length=2, slave_id=1):
    client = ModbusTcpClient(host=host, port=port, timeout=2.0)
    if not client.connect():
        raise ConnectionError(f"Failed to connect to {host}:{port}")

    record_req = FileRecord(file_number=file_no, record_number=record_no, record_length=length)
    resp = client.read_file_record([record_req], slave=slave_id)
    if resp.isError():
        print(f"FC 20 Error: {resp}")
    else:
        for rec in resp.records:
            print(f"File {rec.file_number} Record {rec.record_number}: {rec.record_data}")

    client.close()

if __name__ == "__main__":
    read_plc_file_record()

5. Debugging Modbus Frames With ModbusSimulator

Before deploying telemetry parsers against field relays or RTUs, test register layouts, byte order, and serial/TCP framing using ModbusSimulator (Windows Modbus emulator, Modbus slave simulator, and Modbus TCP simulator). Explore companion protocol guides like FC 24 (Read FIFO Queue) and Modbus Data Types & Byte Order.

Test Modbus TCP & RTU Devices Without Hardware

Download ModbusSimulator for Windows — unified Master + Slave simulator with live register grids, hex frame capture, and 30-day free trial.

Download Free 30-Day Trial

Frequently Asked Questions

What is Modbus Function Code 20 (0x14)?

Function Code 20 is Read File Record, allowing a Modbus master to read numbered files and 16-bit record ranges from extended 6xxxx device memory.

What is Reference Type 0x06 in FC 20?

0x06 is the mandatory identifier defined by Modbus V1.1b3 for file-record sub-requests and sub-responses.

Can one FC 20 request read multiple files?

Yes. You can pack multiple 7-byte sub-requests inside one FC 20 request as long as both the request and response fit inside the 253-byte PDU limit.

What is the maximum Record Number in FC 20?

Per the specification, Record Number ranges from 0x0000 (0) through 0x270F (9,999) per file.